Customer complaint
What the customer noticed
The rooftop air conditioner had stopped cooling and water was dripping into the RV through the return-air vent.
Diagnostic findings
What inspection and testing revealed
Inspection found the evaporator freeze sensor dangling above the return vent instead of being installed in the evaporator coil. Debris was also restricting airflow through the coil, and the air-divider area needed sealing. These conditions supported a suspected evaporator freeze-up, with melting ice likely causing the interior water drip. Evidence of a previous aftermarket refrigerant service connection was also documented.
Work performed or recommended
What Sunset did or recommended
Cleaned debris from the evaporator coil, correctly reinstalled the freeze sensor in the coil, sealed the air-divider area and checked system operation. Documented the aftermarket refrigerant service connection and discussed the finding with the customers.
Outcome and next step
Where the service call stands
The air conditioner drew 8.44 amps and produced a 28.4°F return-to-supply temperature difference. It cooled and operated properly throughout approximately 20–25 minutes of monitored testing after the corrections.